IMLAY/THOMAS: High-Frequency Tests of Line Insulators Sons Company

[Trade Journal]

Publication: American Institute Of Electrical Engineers

New York, NY, United States
p. 2121-2142, col. 1


HIGH-FREQUENCY TESTS OF LINE INSULATORS


BY L. E. IMLAY AND PERCY H. THOMAS


The object of this paper is to present for consideration certain very interesting and suggestive high-frequency insulator tests recently made by the authors. These tests were undertaken to determine the availability of a certain insulator for use on a projected 38,000-volt line and resulted in a radical modification of the design. Having a strictly utilitarian purpose in view, these tests were not expanded to the point that would be desirable from a scientific point of view, although the nature of the results shows the great desirability of further research in this same field. With this explanation the plan of the tests will be understood.

A certain transmission system [Canadian Niagara Power Co.] has used three parallel circuits operating at 22,000 volts to transmit a rather large amount of power some 16 miles for a number of years. The demand for more power has rendered a new line necessary, which is being installed for 38,000-volt operation. The insulators on the old lines are made of electrose having an umbrella petticoat about 12 in. (30.4 cm.) in diameter, and a second smaller petticoat about 6 in. (15.2 cm.) in diameter. They were originally intended to be used on 38,000 volts when the' rise of the load should require. Experience showed that these insulators occasionally punctured through the head from lightning, such failures being very difficult to find. The insulators are mounted on grounded steel pins. This sort of failure was very surprising in view of the fact that these insulators had never been punctured in testing, though they would arc over when wet at about 90,000 volts, as indicated on the primary side of a 25-cycle testing transformer.

It was this discrepancy between the repeated punctures through the head from the conductor to the pin due to lightning, and the steady refusal of the insulators to puncture on a 25-cycle testing set, that led to the high-frequency, high-voltage tests described below.

These tests were made to determine directly whether any difference in the behavior of the insulators could be determined between the use of high frequency and 60 cycles, both produced in the laboratory.

The circuits for the high-frequency tests are shown in Fig. 11.

 

FIG. 1 - ORIGINAL INSULATOR
Fig. 1 - Original Insulator

 

FIG. 2 - PROPOSED 38,000-VOLT INSULATOR
Fig. 2 - Proposed 38,000-Volt Insulator

 

In this figure is indicated a 500-kw., 750,000-volt transformer. One side of this transformer is grounded and the other side connected to the discharge apparatus. The "plate " shown was a sheet iron plate approximately eight by nine ft. (2.4 by 2.7 m.), estimated capacity 0.0001 microfarad, suspended by a cord approximately 3.5 ft. (1.06 m.) from a large transformer tank, which served as a ground plate. The coils marked A, B and C were three air-core choke coils intended to protect the transformer. The coil A was a helix having a diameter of 18 in. (45.6 cm.), and had approximately 22 turns of wire, the turns being spaced approximately three in. (7.6 cm.) apart. The coil B was circular and approximately 24 in. (60.9 cm.) in diameter and had 10 turns. The coil C was a pancake coil and had approximately 200 turns with a mean length of turn of 37.7 in. (95.8 cm.) This coil C was shunted by a graphite resistance of about 125,000 ohms.

The insulator to be tested was mounted on a wooden box some four ft. (1.22 m.) from the floor and had a half-inch (12.7-mm.) brass rod tied in the groove by a band of small size copper wires. The pin carrying this insulator was grounded through a wire approximately six ft. (1.8 m.) long. The length of the lead from the transformer terminal to the condenser plate was approximately 50 ft. (15.2 m.)

A series discharge gap was made by approaching a second brass rod mounted on a wooden stand to one end of the (1.27-cm.) rod tied to the insulator, the second rod being connected to the sheet iron condenser plate by a wire two or three ft. (60 or 90 cm.) long.

Where a measuring gap was used, as recorded in the reports below, this consisted of a needle point gap mounted on hard rubber pedestals located some six ft. (1.8 m.) from the insulator under test. One side of this gap was connected, either with or without resistance, to the conductor on the insulator under test, and the other side was connected to the insulator pin or to the ground.

The general method of test was to raise the voltage of the generator feeding the primary until a discharge occurred across the series gap onto the insulator. With the adjustment of generator voltage and transformer ratio used, the result of the breakdown of the gap was in most cases to so reduce the applied voltage that the arc proper would drop out, at least partially, leaving the series gap nearly intact, and thus the return of voltage on the next alternation would be obliged to nearly reproduce the original breakdown voltage on the gap. The effect of this arrangement was to give a continuous succession of static sparks lasting as long as voltage remained on, that is, one or two seconds, as distinguished from the holding of a continuous arc over the gap. In the tests of June 24th, however, the opposite effect was secured, that is, a single static spark each time the voltage was raised, followed by a mild arc.

The terms "application of voltage" and "trial" used hereinafter mean the raising of voltage to the breakdown point and the cutting off of voltage one or two seconds later.

The results of the various tests have been tabulated as follows, and the tests will be considered briefly in groups.

 

Illustration

 

Illustration

 

Illustration

 

First Group. (Tests 1-2) Normal Flash-Over Test, Dry, in Air, 60 Cycles.

This group of tests was preliminary and was made in the usual manner, the voltage being measured by a spark gap checked approximately by a voltmeter reading on the low-tension winding of the raising transformer. In no case did an insulator puncture. An insulator of the type shown in Fig. 1, that now in use in the three existing lines, flashed over at 122,000 on the second trial; the insulator of the type shown in Fig. 2 flashed over at 150,000 volts. The insulator of Fig. 2 is a new design that was intended to replace the insulator of Fig. 1 and to resist lightning stresses better. The two insulators are the same except that the later design has a head nearly two in. (5 cm.) thick in comparison with a head thickness of one in. (2.5 cm.) in the old insulator of Fig. 1.

Second Group. (Test 3) Normal Flash-Over Test, Wet, in Air, 60 Cycles.

These tests were made with the same electrical apparatus as the first group. Water was thrown on the insulator from three spray nozzles at one side, giving a very heavy "scotch mist." The water dripped very rapidly from the petticoats during the tests, but no direct measurement was made of the amount of water sprayed. The water was relatively pure river water.

The insulator of Fig. 2 flashed over at approximately 95,000 volts.

Third Group. (Tests 4-6) Normal Test Under Oil, 60 Cycles.

The insulators were immersed in good "transil" oil, bubbles under the petticoats and in the pinhole being carefully eliminated. The insulator of Fig. 1 punctured through the head at 205,000 volts, and that of Fig. 2 flashed over the surface, once at 240,000 volts and once at 250,000, except that the lower petticoat was punctured at a point .intermediate between the edge and the central portion in the latter test.

Fourth Group. (Tests 6 1/2-9) High-Frequency Test: apparatus as shown in Fig. 11.

The insulator of Fig. 2, that is, the new insulator with the 2-in. (5-cm.) thickness of head, punctured from the conductor to the pin. The first two insulators tested failed on the tenth to fifteenth applications of voltage, and the third insulator on the second trial.

This result was most surprising, since insulators of this type had flashed over the surface even under oil rather than puncture through the head at 60 cycles. The unusual character of this behavior made a furthur investigation imperative, and the following tests were made.

Fifth Group. (Tests 10-15) High-Frequency Tests as in Fig. 11. (continued.)

Insulators of the type of Fig. 2 were altered in various ways and subjected to the same test. As electrose can be sawed and drilled such alterations could be easily made. The results were as follows:

a. With 1/4-in. (6.3 mm.) hole drilled at the base of the lower petticoat, the insulator failed by puncture through the head on the twenty-fourth trial.

b. With 1 1/4-in. (31.7-mm.) turned off the edge of the upper petticoat, the head failed as before on the sixth trial. This insulator had previously flashed over, as altered, at 60 cycles on 130,000 volts, dry.

c. With four equally spaced 1/4-in (6.3-mm.) holes drilled through the upper petticoat 21 in. (5.7 cm.) from the edge, this insulator punctured in the head on the twenty-eighth trial.

d. With the top petticoat entirely cut off, an insulator punctured in the head on the eighteenth trial. This insulator, as altered, had previously arced over on 60 cycles at 90,000 volts, dry.

e. An insulator with both petticoats sawed off as closely as practicable, leaving a stump about 5 in. (12.7 cm.) high to the tie wire groove and a little over 5 in. (12.7 cm.) maximum diameter, showed no failure in over 150 trials. Apparently this insulator was capable of standing this application of high frequency at 340,000 volts indefinitely.

f. A similar test was made on an insulator as shown in Fig. 1 with 1 1/4 in. (3.1 cm.) turned off the upper petticoat. This punctured the head as usual on the fourteenth trial. Previously this insulator had flashed over the surface on 60 cycles at 130,000 volts.

These results, which were all on electrose insulators, showed most plainly that the resistance to high-frequency stress, in this sort of apparatus at least, bore little relation to its strength against the normal 60-cycle stress. The question naturally arose, were these results peculiar to electrose? Some porcelain insulators were then obtained and high-frequency tests made upon them, as follows:

Sixth Group. (Tests 16-18) High-Frequency Tests, as Shown in Fig. 11.

A porcelain insulator, No. 3007, recommended for 22,000 volts, showed a puncture in the lower petticoat on the second trial, but suffered no further damage in 65 trials. This insulator had previously flashed over at 87,000 volts, dry, 60 cycles.

A porcelain insulator, No. 3012, recommended for 35,000 volts, showed a puncture first on the lower petticoat, then in the middle petticoat and then through the top under the tie wire. This insulator had previously flashed over on 127,000-135,000 volts, dry, 60 cycles.

A porcelain insulator, No. 3002, recommended for 45,000 volts, showed a puncture in the two lower petticoats on the first or second trial and a puncture under the tie wire in a few more trials. This insulator had previously flashed over at 125,000-129,000 volts on 60 cycles,

From these tests on porcelain insulators it appeared that this feature of failure on high frequency was not peculiar to electrose.

It was surmised that the peculiar effect of high frequency was due to a different distribution of electric stresses produced under this condition, which distribution may be assumed to cause a concentration of potential at certain points. Some tests were therefore devised to verify this assumption.

Seventh Group. (Tests 19-21) High-Frequency Tests, as Shown in Fig. 11.

a. A new insulator of the type of Fig. 2 was covered with lead foil about the waist as shown in Fig. 3. This foil was entirely disconnected from any metal parts; but, in view of its electrostatic capacity to the pin, it would change the distribution of potential during the high-frequency attack. Its effect would obviously be toward increasing the effective size of the pin top. This insulator punctured through the head on the 59th trial. It had previously flashed over the surface at 138,000 volts on 60 cycles. While this insulator was not proof against the high frequency, it stood up longer than any of the other electrose insulators, even longer than those with reduced petticoats, except the one without any petticoat. This result is very illuminating, as this insulator had all its petticoats intact.

b. A test was made with a new Fig. 2 insulator with a metal cap, about 4 in. (10 cm.) across, on the top of the insulator. The electrical effect of this should be opposite to that of the lead foil of a above. This insulator showed a puncture in the head on the second trial. This insulator with cap had previously flashed over at 130,000 volts on 60 cycles, dry.

 

FIG. 3 - ELECTROSE INSULATOR OF FIG. 2, WITH BAND OF LEAD FOIL ABOUT WAIST
Fig. 3 - Electrose Insulator of Fig. 2, With Band of Lead Foil About Waist

 

FIG. 4 - TYPE E INSULATOR - ELECTROSE - 22,000 VOLTS
Fig. 4 - Type E Insulator - Electrose - 22,000 Volts

 

c. The same test as "b" was made on a Fig. 1 new insulator and the insulator showed a puncture in the top on the seventeenth trial. This insulator with cap had previously flashed over at 124,000 volts on 60 cycles, dry.

These last three results, while few, indicate pretty clearly the cause of the weakness as well as the nature of experiments required to clarify this matter further.

Those electrose insulators of the type of Fig. 1 which had been in service for some years showed a roughening and a bleaching of the surface to a light gray from the effects of exposure to the weather. Some of these old insulators further showed checks on the surface extending to various depths, mostly on the lower petticoat. Tests were made to get the effect of the weathering on the behavior of the insulator.

 

FIG. 5 - TYPE E INSULATOR - PORCELAIN - 22,000 VOLTS
Fig. 5 - Type E Insulator - Porcelain - 22,000 Volts

 

FIG. 6 - PORCELAIN INSULATOR NO. 3012
Fig. 6 - Porcelain Insulator No. 3012

 

Eighth Group. (Tests 22-24) Weathering Tests, 60 Cycles, Dry.

a. Two old insulators showed a dry flash-over on 60 cycles on 105,000 and on 120,000 volts, respectively, a loss of insulating power of perhaps 10,000 volts. which was undoubtedly due to the arc passing through checks in the lower petticoat. The insulating power of these insulators was thus hardly lessened by the weathering, per se; at least as far as it had then progressed.

b. A third weathered insulator with 1 1/4 in. (3.1 cm.) turned off the edge of the top petticoat flashed over at 108,000 volts, the arc passing through a check on the lower petticoat.

A few days after the completion of those tests, to try still other conditions, a further series of tests was made with results as follows:

Ninth Group. (Tests 25-27) High-Frequency Tests.

These were similar to the previous high-frequency tests, but with the insulator mounted on a wooden pin with tin foil wrapped around the pin up to a point 1/2 in. (12.7 mm.) below the insulator and grounded.

a. An insulator of the type of Fig. 2 punctured through the head, as before, on the ninth trial. This design of insulator (which insulator was newly made for this last set of tests) had previously flashed over the surface at 156,000 volts, dry, 60 cycles.

b. An insulator similar to Fig. 2 but with 12 in. (3.7 cm.) turned off the outer edge of the upper petticoat, punctured through the head, but only after 113 trials. This insulator was nearly at the safety point. This insulator previously flashed over at 129,000 volts, dry, at 60 cycles or at 103,000 volts, wet.

c. An insulator similar to Fig. 2, but with 21 in. (5.7 cm.) turned off the edge of the upper petticoat, resisted 150 trials without puncture. This insulator was found to flash over at 119,000 volts, dry, at 60 cycles and at 81,000 volts, wet, under the rain test already described.

 

FIG. 7 - PORCELAIN INSULATOR NO. 3007
Fig. 7 - Porcelain Insulator No. 3007

 

FIG. 8 - PORCELAIN INSULATOR NO. 3002
Fig. 8 - Porcelain Insulator No. 3002

 

Tenth Group. (Test 28).

The same high-frequency test on electrose insulators of the type shown in Fig. 4 showed no puncture in 150 trials. This insulator flashed over at 115,000 volts, dry, on 60 cycles and 76,000 volts, wet.

Eleventh Group. (Tests 29-30).

The same high-frequency test on a porcelain insulator of the type shown in Fig. 5 showed a puncture from the tie wire groove to the pin top, on the third trial in the case of one insulator, and on the second trial on another insulator. This type showed a flash-over at 118,500 volts, dry, at 60 cycles, in one case, and at 95,000 volts in a second case, and a flash-over of 70,000 volts, wet, on the first insulator.

These tests of groups 9 to 11 show that the use of a wooden pin, extending only a short distance out from the threaded portion of the insulator, considerably increased its power to resist the high-frequency stress. This result must be due to the prevention of the ground potential from getting up inside the insulator, so to speak. Its effectiveness is, however, somewhat limited by the fact that extremely severe potential shocks, such as were here produced, tend to cause a discharge over the surface of the pin into the insulator pin recess. If this pin were cemented air-tight into the insulator the result would presumably be to increase the power of the insulator to stand high-frequency tests.

Certain other tests which are of interest were made to measure the actual voltages reached on the insulator during discharge. Measurements were made by noting the voltages that were required to jump the spark gap marked "measuring gap" in Fig. 11, under certain discharge conditions.

a. During the high-frequency test on a Fig. 2 insulator, (test 8), sparks were observed in the measuring gap when it was set at 10 in. (25.4 cm.), 104,000 volts, (needle points) but no sparks occurred when it was at 11 in. (27.9 cm.), 112,000 volts. There were 125,000 ohms (seven composition sticks) in the shunt measuring gap circuit when these readings were taken. This indicates a maximum voltage during the high-frequency attack of slightly over 100,000 volts. This result, which should be compared with the 150,000 (15-in. or 38-cm. gap) necessary to make the insulator flash over at 60 cycles, shows that there must have been a great local concentration of voltage on portions of the insulator at the high frequency. This is an important point in connection with surges produced by internal causes. If a 100,000-volt static voltage will pass over or through an insulator which flashes over at normal frequency only on 150,000 volts, this fact should be recognized.

b. With the same arrangement as in "a" above, except that the insulator was short-circuited by a No. 18 copper wire, drawn tight between pin and tie wire groove, a voltage sufficient to jump a needle gap corresponding to 15,000 volts was noted, and no spark occurred over the gap when set for 20,000 volts. No resistance was used in the measuring gap circuit in this test.

c. With the conditions of test "b" above, except that five separate No. 18 wires were used to short-circuit the insulator, located at points equally spaced around its circumference, a spark gap of 2 in., (12.7 mm.), corresponding to 10,000 volts, was jumped, but no spark was found with the spark gap set at a value to indicate 15,000 volts. No resistance was used in the measuring gap circuit in these tests.

 

DISCUSSION OF TESTS

 

The obvious meaning of these tests is of great import. Unless there is some reason for believing that the tests are only of limited application or are rendered misleading by some unobserved condition, they mean that many of the line insulators now in service may be expected to break down by puncturing under the attack of lightning rather than by discharge over the surface, which latter is recognized as the desired characteristic. And this in spite of the fact that these insulators may have been thoroughly tested on normal frequencies in the usual way and may have then always flashed over the petticoats as intended. The fact sho