High Voltage Transmission Part I

[Trade Journal]

Publication: The Electrical Engineer

New York, NY, United States
vol. 26, no. 551, p. 519-520, col. 1-2


High Voltage Power Transmission. -- I.

BY CHAS. F. SCOTT.

OBJECT OF INVESTIGATION.

 

SEVERAL years ago an investigation of the conditions and requirements incident to the use of high voltages was undertaken by the engineering department of the Westinghouse Electric & Manufacturing Company. In this experimental investigation the size of the apparatus and the conditions of the tests were as far as practicable such as would prevail in actual work.

The transformer, the sine qua non of high-voltage working, received first consideration. A design suitable for large sizes was worked out and tested; then high-voltage windings were made. Attention was next directed to the line insulator. New forms and sizes were designed, made and tested to determine the losses which would occur and the limit at which they would break down.

The luminosity and the hissing sound emitted by the connecting wires of high voltage, suggested a loss which might be an appreciable addition to that over the surface of the insulators. It was found that a very considerable loss of energy took place between the wires-a loss which at high voltages was much in excess of that across the surface of the insulators.

The tests, the author states, were undertaken at Telluride con jointly with Mr. L. L. Nunn, a pioneer in power transmission work, and the results of the work at this place were so assuring that the Telluride Power Transmission Company has lately installed a plant which is in commercial operation at 40,000 volts, and is now making an increase in the plant.

 

HIGH TENSION TRANSFORMERS.

 

In 1891 the Westinghouse Company furnished transformers for the 10,000- volt transmission to San Bernardino and Pomona. Twenty transformers were used in a set, each giving a pressure of 500 volts and the twenty in series 10,000 volts. This arrangement made the insulation within the individual coils a matter of comparative ease. The insulation between the coils of the high tension circuit and other parts of the transformer was secured by allowing a space which was filled with oil.

The first arrangement of transformers for giving from 30,000 to 50,000 volts was made by using a number of transformers, each giving 10,000 or 15,000 volts. A large transformer was designed in January, 1894. The output of 200 k. w. was many times greater than that of any transformers which had been made by the Westinghouse Company. The transformer was oil-insulated and was cooled by water flowing through a pipe immersed in the oil. This transformer was pronounced a success, and the type was adopted and has been followed ever since as a standard, except that the water- cooling is employed only on the largest sizes.

The transformer was then rewound for 40,000 volts, and a somewhat reduced output. It was operated at this voltage for a short time, when it was found that through an oversight, the insulation between layers was insufficient. In October the high tension coils were rewound for 60,000 volts and the transformer is still in use after many months of varied service and a considerable period of inactivity.

 

HIGH TENTION INSULATORS.

 

After a high-voltage transformer was constructed, the insulator naturally presented itself as a fundamental factor in transmission. The requisites of an insulator for high-voltage work are, that it shall have a dielectric strength sufficient to prevent the current passing directly through the material, that its dimensions shall be large enough to prevent the passage of current over the outside of the insulator to its support, and that the resistance, both of the material and its surface, shall be sufficiently high to prevent undue loss of energy. In addition to these fundamental electrical requirements are those of a mechanical nature involving strength and convenience. These properties must of course be permanent, and not liable to deterioration while in service.

A much larger glass insulator was made having the so - called "helmet" form, which was probably the beginning of a type which is now quite common. The large glass insulator presented mechanical difficulties in manufacture and recourse was had to porcelain.

An interesting evolution then began to take place in the manufacture of porcelain. There were eight or ten steps in this history, in which insulators which were presumed by the manufacturer to be satisfactory were broken down on high-voltage test. Porcelain which presented a beautiful smooth glazed surface was often found to contain internal cracks or cavities which were soon traversed by the current. In other cases bits of pebbles or other impurities were found. In still other cases the porcelain was not homogeneous and was not compact, or the material was porous and absorbed a drop of ink almost as readily as a lump of sugar would do.

The under-hung form of porcelain insulator, the first form employed, did not prove successful nor satisfactory. The insulator was heavy and cumbersome, and no satisfactory method was de vised for holding the wire.

Some measurements were made of the losses on the Pomona 10,000-volt transmission line insulators. Twenty-four insulators were mounted on wooden pins. A wire was run along the tops of the insulators and a second wire connected the pins. The increase produced in the reading of a wattmeter in the primary of the raising transformer when the wires were connected to the high-voltage terminals, was taken as the loss on the insulators. The loss at 25,000 volts was about two watts per insulator. This voltage between pin and wire corresponds to 50,000 volts between transmission wires.

 

LOSSES BETWEEN WIRES.

 

The loss over the surface of insulators was quite small, in fact almost insignificant compared with the amount of power which would ordinarily be transmitted. The various displays of energy about high-tension wires, led us to investigate and determine whether this loss was one of importance. In order to measure the loss between wires, eliminating what occurs on the insulators, it was desirable to have a considerable length of wire, to support it without insulators, and preferably to arrange the wires in such a form as to give a considerable loss. Nine wires each 60 feet long were stretched 4 inches apart in a horizontal plane and were held in place by strings several feet in length at each end. The wires were No. 19 B. and S. gauge, 0.036 inch in diameter. They could be connected in various ways, and any pair or pairs of wires could be omitted as desired.

The wires began to give a hissing or crackling sound and in the dark began to appear luminous at a little below 20,000 volts. As the voltage was increased the sound became more and more intense, the wires vibrated and became more and more luminous, until at the higher voltages they were surrounded by a coating of soft blue light many times the diameter of the wire. Often there were bright points along the wire, probably corresponding to bits of dust or rough places resembling points on the wire. The large room soon became strongly charged with ozone.

The results of the measurements which are presented by the author in the form of curves, show that while the loss in the transformer is less at the higher frequency the loss on the high- tension wires is almost the same for both frequencies, namely, 60 and 133 periods per second. These losses are very small below 18,000 volts, but increase rapidly up to 30,000 volts, which is about the highest pressure used.

Measurements made upon wires at greater distances show that the action is considerably less as the wires are separated. The loss is approximately the same at 28,000 volts when the wires are 4 inches apart that it is at 36,000 volts when they are 16 inches apart. The loss for a distance of 8 inches is intermediate.

Other measurements were made, but nothing of further importance was developed. It is interesting to note that within a few days of the first measurements the general characteristics of this loss were determined, namely, that the loss between wires increases rapidly after a critical voltage is reached, that the loss is practically independent of the frequency, that it is much less as the distance between wires is increased. When a loss of 1,200 watts was obtained on a total length of 540 feet of wire at only 30,000 volts, the important bearing of this phenomenon upon transmission became very evident. The tests were stopped as preparations were begun for the continuation of the work at Telluride.

 

TRANSFORMERS AT TELLURIDE.

 

The original Telluride plants operated at 3,000 volts. Both the generator and the synchronous motor were wound for this pressure. Two transformers were furnished for the high-voltage tests, one for raising the generator voltage for transmission and the other for lowering the voltage for the motor. The windings were connected with a number of terminals by which the high tension voltage could be varied over a wide range up to 60,000 volts.

Coils of similar shape were placed side by side in what is known as the "parallel" form of construction. Each coil had many layers of wire and but few turns per layer, thus securing a small difference of pressure between consecutive layers. The high-tension winding was divided into four similar coils, each designed to give a maximum of 15,000 volts. The individual coils could be differently connected, either in series or in multiple. The low-tension coils were five in number and were provided with loops, by which the number of effective turns could be varied. Three low-tension coils were placed between two pairs of high-tension coils and the two remaining low-tension coils were placed on the two ends. Between the low-tension and high-tension coils metallic shields were placed, which were connected to the ground for protecting the low-tension circuit from danger in case of accidental contact with the high-tension circuit and also for screening the low-tension circuit from electrostatic induction from the high-tension windings. The transformer was immersed in a case containing oil. The iron and the case of the transformer as well as the shields between the coils were connected to the ground.

There was also an auxiliary transformer whose primary was connected across the generator terminals while its secondary was placed in series with the circuit to the raising transformer, thus either raising or lowering the generator e. m. f. as desired. The secondary had a number of steps so that the voltage could be varied at will.

 

THE TRANSMISSION LINE.

 

The line extends from the power station near Ames, which is a few miles from Telluride, Col., to the Gold King mill. The line passes over an exceedingly rugged country and has a total length of nearly 24 miles (11,720 feet). There are 62 poles, each carrying three cross-arms, the upper being about 26 feet from the ground. Each cross-arm carries two wires supported by insulators which are designated as follows: Large glass, small glass, porcelain. The large glass insulator is the same as that used on the circuit in the San Bernardino and Pomona plant. The total height is 5 inches and the maximum diameter 5˝ inches. The bottom of the insulator stands 14 inches above the cross-arm. The porcelain insulator is 4-1/16 inches high and 5-7/8 inches in diameter. The bottom is 3-1/16 inches above the cross arm. The small glass insulator is 3˝ inches in height, 44 inches in diameter and stands 2-1/4 inches above the cross- arm. This insulator is triple petticoat; the other two insulators are double petticoat. The circuits were strung with galvanized iron wire 0.165 inches in diameter, which is No. 8 B. W. G., and about No. 6 B. and S. gauge. Later the circuit on porcelain insulators was changed to No. 6 B. and S. copper wire 0.162 inches in diameter. The measured resistance of one of the iron wire circuits was 66.25 ohms at -7 deg. C.

 

THE LIGHTNING PROTECTION.

 

The lightning protection was laid out by Mr. A. J. Wurts, who previous to this time had spent some months at Telluride, determining the requirements for protecting the 3,000- volt circuit. The protection consists of choke- coils and spark- gaps of non-arcing metal, as described by Mr. Wurts in his paper before the Institute, March, 1892.

In each line ten choke-coils were placed. Unit arresters were used each consisting of seven non-arcing metal cylinders and having six spark-gaps.

The author then describes the tests made at Telluride and gives a discussion of the results as well as a general résumé and conclusions. These will be reproduced in our next issue.

--

Keywords:General
Researcher notes: 
Supplemental information:Articles: 11160, 11127, 11117
Researcher:Bob Stahr
Date completed:January 17, 2023 by: Elton Gish;